iG5A

Features

Features

  • - Selectable V/f, sensorless vector control
  • - Motor parameter Auto-tuning
  • - Powerful torque at overall speed range
  • - 0.1 ~ 400Hz frequency output
  • - -15% ~ +10% input voltage margin
  • - Fault history: Last 5 faults
  • - 0~10Vdc / -10 ~ +10Vdc analog input
  • - IP20 enclosure, UL Type 1 (Option)
  • - Selectable manual/automatic torque boost
  • - Selectable PNP/NPN input signal
  • - 2nd motor control and parameter setting
  • - Built-in Dynamic braking transistor as standard
  • - Enhanced process PID control
  • - Built-in RS485 (LS Bus / Modbus RTU) communication
  • - Cooling fan On/Off control & Easy change
  • - Remote control using external keypad * RJ45 cable(Optional)
  • - Upgraded functions:
    • · Sleep & Wake-up (Energy savings)
    • · KEB(Kinetic Energy Buffering) protection
    • · Low leakage PWM algorism
  • - Monitoring & commissioning PC based software tool (Drive View)

Specification

Specification

1Phase 200V

Specification - 1Phase 200V
SV ㅁㅁㅁ iG5A-1 004 008 015
Motor Rating [HP] 0.5 1 2
[kW] 0.4 0.75 1.5
Output Rating Capacity [kVA] 0.95 1.9 3.0
FLA [A] 2.5 5 8
Frequency 0.1 ~ 400 [Hz]
Voltage [V] 3 Phase 200 ~ 230V
Input Rating Voltage [V] 1 Phase 200 ~ 230 VAC (+10%, -15%)
Frequency 50 ~ 60 [Hz] ( ± 5%)
Cooling Method Forced Air Cooling
Weight [kg] 0.76 1.12 1.84

3Phase 200V

Specification - 3Phase 200V
SV ㅁㅁㅁ iG5A- 2 004 008 015 022 037 040 055 075 110 150 185 220
Motor Rating [HP] 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
[kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Output Rating Capacity [kVA] 0.95 1.9 3.0 4.5 6.1 6.5 9.1 12.2 17.5 22.9 28.2 33.5
FLA[A] 2.5 5 8 12 16 17 24 32 46 60 74 88
Frequency 0.1 ~ 400 [Hz]
Voltage [V] 3 Phase 200 ~ 230V
Input Rating Voltage [V] 3 Phase 200 ~ 230 VAC (+10%, -15%)
Frequency 50 ~ 60 [Hz] ( ± 5%)
Cooling Method Self Cooling Forced Air Cooling
Weight [kg] 0.76 0.77 1.12 1.84 1.89 1.89 3.66 3.66 9.0 9.0 13.3 13.3

3Phase 400V

Specification - 3Phase 400 V
SV ㅁㅁㅁ iG5A- 4 004 008 015 022 037 040 055 075 110 150 185 220
SV ㅁㅁㅁ iG5A- 4 004 008 015 022 037 040 055 075 110 150 185 220
Motor Rating [HP] 0.5 1 2 3 5 5.4 7.5 10 15 20 25 30
[kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Output Rating Capacity [kVA] 0.95 1.9 3.0 4.5 6.1 6.9 9.1 12.2 18.3 22.9 29.7 34.3
FLA[A] 1.25 2.5 4 6 8 9 12 16 24 30 39 45
Frequency 0.1 ~ 400 [Hz]
Voltage [V] 3 Phase 380 ~ 480V
Input Rating Voltage [V] 3 Phase 380 ~ 480 VAC (+10%, -15%)
Frequency 50 ~ 60 [Hz] ( ± 5%)

Download

検索

FAQ

自動化ソリュ-ション
グリーンビジネス電力ソリュ-ション自動化ソリュ-ション
Low Voltage VFD
Process AutomationLow Voltage VFDMedium Voltage VFDServo Drive & Motor (XGT Servo System)SoftstarterRemote I/OHMIPLC
iG5A
iV5L S100H100iG5A iS7 iP5A iV5 iE5 iC5 [Discontinued] iS5
iG5A
iG5A

販売店をご確認ください。

ショートカット
  • Technical Question iG5A

    [iG5A] Stop motor under PID control

    The minimum value of F23 is 0.1Hz. If you want to stop motor under PID control, please use Sleep and Wake-up function. The related parameters are frome H61 to H63.
  • Technical Question iG5A

    [iG5A] Parameter Read/Write

    [Parameter read] and [Parameter write] can be seen only when you perform the remote operation. They just read and write the saved parameters from the body of the inverter to remote keypad without saving parameters. As Parameter Read/Write performance is finished, the set value of 1 is changed to 0 automatically.
  • Technical Question iG5A

    [iG5A] Carrier Frequency

    By raising carrier frequency, you can reduce the noise of motor. In case of iG5A, you can adjust it up to 15kHz.
  • Technical Question iG5A

    [iG5A] EEP TRIP

    EEP trip [Parameter save error] occurs by incomplete S/W dwonload or CPU error. When CPU gets damage, user-setting parameters can't be entered into memory.
  • Technical Question iG5A

    [iG5A] Elevator Application

    Basically for elevator application, we recommend you to use iV5. It is difficult and dangerous to apply iG5A for such applications as we can't gurantee low speed torque or normal accel/decel performance as vector dedicated Inverter does.
  • Technical Question iG5A

    [iG5A] Distance between inverter and motor

    Generally, we recommend to wire up to 200M for the maximum. You should adjust the carrier frequency as the wiring distance increases, and use micro surge filter if needed.